This zone type must NOT be used for wireless zones. Activation of a keyswitch zone is intended to arm or disarm the system. Activation of the zone will
not log or transmit the Police code. A bypass on this zone type will not be un-bypassed when the system is disarmed. When the zone is bypassed, a zone
bypass event buffer log and communication occurs immediately, NOT when the system is armed.
With an audible alarm active, using the keyswitch when disarmed is the same as entering an access code at the keypad. Activating this zone type during
the first 30 seconds of a delayed fire alarm is the same as pressing a key at the keypad (the 90 second delay will start). If left in the violated state, the
system will not arm until the zone is restored and violated again.
24
For Future Use
25
Interior Delay Zone: This zone type is normally used with motion detectors and has a standard exit delay time.
If the panel is Away armed, the Interior Delay Zone will be active at the end of the exit delay. The zone then acts like an interior type zone [04]. If the
panel is Stay armed, a violation of this zone type initiates Entry Delay 1. Violating this zone during exit delay will not cause the system to arm in Away
mode, as in regular delay type zones.
26
24 Hour Non-Alarm (or local alarm) Zone. Zones programmed as this type are active at all times but do not cause an alarm, and are not saved in
alarm memory. Zone attributes such as Zone Bypassing and Door Chime will affect the functionality of this zone.
i
This zone type will sound the bell, but not communicate during a walk test. Tampers and faults on zones programmed as 24-Hour non-alarm type will
not cause alarms.
27-30
For Future Use
31
Day Zone. Violating this zone when disarmed will sound the keypad buzzer but will not log or report the events. Violating this zone when armed will
sound the bell and communicate the event.
32
Instant, Stay-Away Zone. This zone is bypassed when the system is Stay armed, but it functions similarly to an Instant Zone [03] when Away armed.
This zone type is useful for motion detectors that must NOT follow the entry delay after a delay zone is violated, but must still retain the Stay/Away
functionality.
33-35
For Future Use
36
24-Hour Non-Latching Tamper Zone. This zone generates a tamper condition when violated. This zone is active when armed or disarmed.
37
Night Zone. This zone acts like an interior Stay/Away zone [05] when the panel is armed in any method except the following. When the system is
armed in Stay mode and the interior zones are reactivated by the user entering [
][1], this zone type will not be activated.
81
24-Hour Carbon Monoxide (CO) Detection. This zone type is used with a wireless CO detector. This zone definition has a distinct bell cadence in
the event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then repeated. After 4 minutes
the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is entered or the bell times out.
82
Audio Verification Monitor. This zone type is used with the PC5950 audio verification module. This zone definition is used to force mute the bell and
sirens during a 2-way audio session.
87
Delayed 24-Hour Fire (Wireless). This zone is used with wireless smoke detectors. This zone functions similar to the standard 24 hour fire zone,
except the alarm memory and transmission by the communicator is delayed 30 seconds. If the alarm is acknowledged by pressing any key within 30
seconds, the bells will silence and the transmission will be aborted. If the smoke detector is not restored after the alarm has been acknowledged the bell
output will activate after 90 seconds. The user then has another 30-second delay before the bell output latches and communications are activated. A
code is then required to silence the bell output. A tamper or fault of this zone type will cause a fire trouble to log and transmit.
i
The fire delay is terminated if a second fire zone is tripped or if the key is pressed during a delay.
88
Standard 24-Hour Fire (Wireless). This zone is used with wireless smoke detectors. The bell output will sound instantly to indicate that the smoke
detector has been activated when violated. If enabled, the communicator will immediately transmit the alarm to the monitoring station. A tamper or
fault of this zone type will cause a fire trouble to log and transmit.
i
Zone attributes should NOT be changed from the default settings for all fire type zones.
89
Auto Verified Fire Zone (Wireless) (Required for CP-01). This zone type is to be used with wireless smoke detectors. This zone definition ensures
an alarm condition persists by looking for a second alarm transmission or the absence of an alarm restoral condition. The system ignores subsequent
alarm transmissions after the first transmission from the same zone for a duration of 40 seconds. If the sensor is in an alarm condition at the end of this
40-second delay, the system will go into full alarm, sounding the bell, logging and communicating the event. If the zone is in a restored condition at the
end of the 40-second delay, the system will start another 80 second verification time sequence. If a fire zone goes into alarm during this period, the sys-
tem will go into full alarm, sounding the bell, logging and communicating the event.
i
A tamper or fault of this zone type will cause a fire trouble to log and transmit.
The wireless smoke detector that is used with this zone type must have a built-in siren to act as a pre-alert to the system alarm.
Multiple Fire Detections: If another device detects fire during the auto verify or delay sequence, the sequence is immediately terminated and alarms
are generated for all pending zones. This applies to all other fire zones or system key alarms on the system (i.e., two fire alarms from different
devices on the system will cancel all pending fire delays and create immediate alarms).