2 Installation
2-6
To perform a global placement test on a zone, type [00]. In this mode, all wireless zones, keypads and sirens are placement tested at the same
time. To perform another individual placement test on a zone, exit the global placement test by pressing [#] and begin a new placement test.
3. Place the wireless device(s) in the intended mounting location(s).
4. Activate the device(s) as described in the associated installation sheet.
• If the alarm system receives a STRONG signal, the bell sounds once and “Location is Good” is displayed on the LCD.
• If the alarm system receives a WEAK signal, the bell sounds 3 times and “Location is Bad” is displayed on the LCD.
• If the alarm system indicates no response, reposition the wireless device(s) and repeat the test.
• For individual placement tests, repeat step 2-3 for each device.
5. When placement testing is complete, press [#] to exit Installer Programming.
2.5 Individual Wireless Device Placement Test for Sirens and Keypads
Individual placement testing can be performed on wireless sirens and keypads. Use the scroll keys or enter a 2-digit entry to select a specific key-
pad or siren, depending on which placement test section is entered.
Wireless Device Placement
1. To individually test keypads or sirens, press:
[ ✱ ][8][XXXX][905] - for wireless keypads
[
✱ ][8][XXXX][906] - for wireless sirens
NOTE: [XXXX] represents the installer code (default 5555).
2. Type 1 to 4 for keypad/siren 1-4 or scroll to the desired device and press [ ✱ ] to begin the individual placement test.
3. Place the wireless device in the intended mounting location.
4. Activate the device as described in the associated installation sheet.
• If the alarm system receives a STRONG signal the bell sounds once and “Location is Good” is displayed on the LCD.
• If the alarm system receives a WEAK signal the bell sounds 3 times and “Location is Bad” is displayed on the LCD.
• If the alarm system indicates no response, reposition the wireless device and repeat the test.
5. Repeat Step 2-3 for each device. Once the placement test is complete for the device, press [#] once to select the next similar device.
6. When placement testing is complete, press [#][#][#] to exit Installer Programming.
2.6 GPRS/Ethernet Module Setup/Initialization
After system installation and programming, ensure that the following sections are programmed:
• Central Station Phone Number, (Template Programming - Entry 5) (if applicable, in sections [301]-[303] & [305])
• Account code, section [310], (Template Programming - Entry 6)
• Communications Format, Section [350]- set to [03] Contact ID or [04] SIA FSK
• GPRS/Ethernet Module Enable section [382] Option[5] - set to GPRS/Ethernet Module Enabled
i
Two-way wireless keys must be activated by pressing any key before they become functional.
To placement test a wireless keypad, press number keys 0-9.
To placement test a wireless siren, press the Test button or tamper the device.