Appendix D: Regulatory Approvals Information
APP-9
SIA False Alarm Reduction Installations
For a list of the defaults value programmed when the unit is shipped from the factory and for any other programming information refer to table below.
Caution: Call Waiting Cancel (section [382], Option 4) feature on a non-Call Waiting line will prevent successful communication to the supervising station.
Fire Alarm Verification feature (Auto Verified Fire Zone type [89]) is supported on the DSC Wireless Smoke Detector, Model WS4916. The fire alarm delay is 40s.
Notes: Programming at installation may be subordinate to other UL requirements for the intended application
Cross zones have the ability to individually protect the intended area (e.g., motion detectors which overlap)
Cross zoning is not recommended for line security Installations nor is it to be implemented on exit/entry zones.
This pannel has a communication delay of 30 seconds. The delay can be removed or it can be increased up to 45 seconds at the request of the end user in consultation with the
installer.
Do not duplicate any reporting codes. This applies to all communication formats other than SIA or CID sending automatic programmed reporting codes.
The security system shall be installed with the sounding device activated and the communicator enabled for transmission using SIA or CID format.
SIA Feature
Programming Section
Comments Range/Default Requirement
Exit Time
[005], 3rd entry
Access to entry and exit delays and bell time out for the system
Range:
45- 255 seconds
Default:
60 sec.
Required
(programma-
ble)
Progress Annunciation/
Disable - for Silent Exit
[014], Option 6 ON
Enables audible exit beeps from the keypad for the duration of exit delayKeypads may be disabled
Default:
Enabled
Allowed
Exit Delay Restart Enabled
[016], Option 2 ON
Enables the exit delay restart feature
Default:
Enabled Required
Auto Stay Arm on
Unvacated Premises
[001]-[002] Zone type 05, 06, 32
Function Key: Stay Arming. All Stay/Away type zones (05, 06) and Instant Stay/Away
zones (32) will be automatically bypassed
If no exit after full arm
Default:
Enabled
Required
Exit Time and Progress
Annunciation/Disable
or Remote Arming
[005] and [014] bit 6
System times and audible exit beeps can be disabled when using the wireless key to
Away Arm the system
Default:
Enabled Allowed
Entry delay(s)
[005], 1st and 2nd entry
Access to entry and exit delays and bell time out for the system
Note:
Combined entry delay and communications delay (Abort window) shall not
exceed 60s
Range:
30 sec. to 4 min.
Default:
30 sec.
Required
(programma-
ble)
Abort Window
for Non-Fire zones
[101]-[134] bit 7 ON
Access to zone attributes, i.e., swinger shutdown, transmission delay and cross zone.
Individual zones attribute bit 7 (Transmission delay) is by default ON
May be disabled
by zone or zone type
Default:
Enabled
Required
Abort Window - for
Non-Fire zones
[377], 4th entry
Access to the programmable delay before communicating alarms
Note:
Combined entry delay and communications delay (Abort window) shall not
exceed 60s
Range:
15 - 45 sec.
Default:
30 sec.
Required
(programma-
ble)
Abort Annunciation
[382], Option 3 ON
Enables the “Communication Cancelled” message display on keypadAnnunciate that no
alarm was transmitted
Default:
Enabled
Required
Cancel Annunciation
[328], 8th entry
Access to the reporting code for alarm cancelled Annunciate that a
Cancel was transmitted
Default:
Enabled
Required
Duress Feature
[*][5] Master Code
Option 2 ON
Do not derive code from an existing Master/User code (e.g., Master code is 1234, the
duress code should not be 1233 or 1235)
No 1+/- derivative of another
user code. No duplicates with
other user codes
Default:
disabled
Allowed
Cross Zoning
[016] Option 1
[101]-[134] bit 8 OFF
This option enables cross zoning for the entire system. Individual zones can be
enabled for cross zoning via zone attribute bit 8 in sections [101] - [134]
Programming required
Default:
Disabled
Required
Cross Zone Timer
[176]
Access to the programmable cross zone timer May program
Range: 001-255 sec./min.
Default:
60 seconds
Allowed
Swinger Shutdown for Alarms
[377] 1st entry
Access to the swinger shutdown limit for zone alarms For all non-fire zones
shut down at 1 or 2 trips
Default:
1 Trip
Required
(programma-
ble)
Swinger Shutdown Enable
[101] - [134] bit 6 ON
Access to zone attributes, i.e., swinger shutdown, transmission delay and cross zone.
Individual zones attribute bit 6 (Swinger Shutdown enabled) is by default ON
For non-police
response zones
Default:
Enabled
Allowed
24-Hr. Auto-verified Fire
(Wireless) Zone type [89]
Access to 24-Hr. Auto-verified fire (wireless)Activates If a restoral is Not
received within the specified
time
Default:
disabled
Required
Call Waiting Cancel Dial String
[304], [382], Option 4 OFF
Access to the dialing sequence used to disable call waiting Dependant on user phone
line
Default:
disabled
Required
Testing
System Test:
[*][6] Master Code, Option 4
The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn on.
Refer to the User Manual (part no. 29007326).
Walk Test Mode:
[*][6] Opt 8
This mode is used to test each zone on the system for proper functionality.